Project Overview

Culver Boulevard Apartment Building

Scope of Work

  1. Provide installation of a new overhead fire sprinkler system throughout proposed mixed-use, 5-story apartment over one level of subterranean parking, as shown on provided plans and specifications. 
  2. Building construction is type V-A/I-A. Systems to comply with the LADBS (City of Los Angeles Building and Safety) as well as NFPA-13, 2019 requirements for R-2, S-2, M occupancies.  
  3. Sprinkler coverage will be provided throughout structure. Heads will be spaced for ordinary & light occupancies. Fire sprinkler spacing to be a maximum of 130 sq. ft. & 256 sq. ft. in light hazard areas. 
  4. Precision Fire’s point of connection to be 6” above finished grade. 
  5. Fire sprinkler riser to include electronic flow switch, and electronic 10-inch fire bell (installation of bell by others & wiring to bell and flow switch also to be done by others) 
  6. Fire sprinklers in new scope of work to be new quick response per NFPA 13 2019. 
  7. All above ground piping shall be steel sch. 7, 10, 30 & 40 with threaded and or grooved/mechanical fittings.  
  8. Work shall include all materials, labor, plans and plan submittal, city business license, rough & final fire sprinkler inspections. 
  9. Design-Build Engineering will be provided with our services. 
  10. Copies of Permits & Approved Fire Sprinkler Plans to be provided to Client upon request. 