Project Overview

Lull – Goleta 

Scope of Work

  1. New sprinkler coverage will be provided below new suspended and hard lid ceilings only as shown on provided plans and specifications.  
  2. Existing Fire Sprinkler drops shall be demolished to the branch line in open areas. 
  3. All existing excessive fittings and elbow fittings that do not need to serve the system shall be removed and plugged at branch line outlet. 
  4. Upright coverage shall be modified to NFPA Code at all full height walls. 
  5. Existing upright sprinkler heads will be protected for painters to paint the ceiling and pipe. 
  6. Heads will be spaced light hazard for “B” occupancies.  
  7. Fire Sprinkler Heads installed under T-Bar shall be center of tile respectively.  
  8. Fire sprinklers in new scope of work to be new quick response per NFPA 13 2019. 
  9. All piping to be added and/or relocated are to meet local and NFPA 13 2016 standards and the County of Santa Barbara Fire Department. 
  10. Work shall include all materials, labor, plans, shop drawings, plan submittalrough and final inspections. 