PROJECT: Regency Palms - Palmdale

PROJECT STATS

    • Industry
    • Residential
    • Location
    • Palmdale, CA

Project Overview

Regency Palms – Palmdale

Scope of Work

  1. Provide installation of a new overhead fire sprinkler system throughout proposed Assisted Living Building, as shown on provided plans and specifications. 
  2. Upright coverage shall be provided in attic space. 
  3. Building construction is type V-A. Systems to comply with the County of Los Angeles Fire Department as well as NFPA-13, 2016 requirements for R-4 & B occupancies.  
  1. Sprinkler coverage will be provided throughout structure. Heads will be spaced for ordinary & light occupancies. Fire sprinkler spacing to be a maximum of 256 sq. ft. 
  2. Work shall include all materials, labor, plans and plan submittal, rough & final fire sprinkler inspections. 
  3. Fire sprinklers in new scope of work to be new quick response per NFPA 13 2016 
  4. Fire sprinkler riser to include electronic flow switch, and electronic 10-inch fire bell (installation of bell by others & wiring to bell and flow switch also to be done by others) 
  5. All above ground piping shall be steel sch. 7, 10, 30 & 40 with threaded and or grooved/mechanical fittings.  
All ()
Commercial ()
Residential / Hospitality ()
Industrial ()
Education ()