PROJECT STATS

    • Industry
    • Residential
    • Location
    • Santa Barbara, CA

Project Overview

Residential Project – Santa Barbara

Scope of Work

  1. Provide full fire sprinkler coverage throughout proposed residence as required per NFPA 13D and jurisdiction requirements of City of Santa Barbara Fire Department
  2. Building construction is type V-B. Systems to comply with the City of Santa Barbara Fire Department as well as NFPA-13D, 2019 requirements for “R3” occupancies.
  3. Sprinkler coverage will be provided through out structures. Heads will be spaced for light hazard residential, fire sprinkler spacing to be at maximum 256 sq. ft.
  4. All sprinkler heads shall be quick response concealed.
  5. Fire sprinkler riser to include, electronic flow switch, and electronic 6-inch fire bell (installation of bell, wiring of bell & flow switch by others)
  6. Work shall include all materials, labor, plans, design calculations, shop drawings, design coordination meetings, plan submittal, rough & final fire sprinkler inspections.
  7. Custom Fire Sprinkler Covers available upon request outside white, black or chrome.