PROJECT STATS

    • Industry
    • Hospitality
    • Location
    • Oxnard, CA

Project Overview

Starbucks – Oxnard

Scope of Work

  • Provide installation of a new overhead fire sprinkler system throughout trash enclosure.
  • Building construction is type I-A & approximately 153 ft.² in total area floor area. Systems to comply with the City of Oxnard Fire Department as well as NFPA-13, 2013 requirements for S-2 occupancies.
  • Sprinkler coverage will be provided throughout structure. Heads will be spaced for ordinary occupancies. Fire sprinkler spacing to be a maximum of 130 sq. ft.
  • Fire sprinklers in new scope of work to be new quick response per NFPA 13 2016
  • Fire sprinkler riser includes electronic flow switch, and electronic 10-inch fire bell (installation of bell by others & wiring to bell and flow switch also to be done by others)
  • All above ground piping shall be steel sch. 7, 10, 30 & 40 with threaded and or grooved/mechanical fittings.
All ()
Commercial ()
Residential / Hospitality ()
Industrial ()
Education ()