PROJECT STATS
-
- Industry
- Residential
- Location
- Los Angeles, CA
Project Overview
PROJECT: Echo Park Condos – Los Angeles
Scope of Work
Scope of work:
- Provide installation of a new overhead fire sprinkler system throughout proposed 4-story apartments over 1 level of podium parking, as shown on provided plans and specifications.
- Building construction is type V-A over I-A. Systems to comply with the City of Los Angeles Building and Safety as well as NFPA-13, 2013 requirements for R-2 & S-2 occupancies.
- Sprinkler coverage will be provided throughout structure. Heads will be spaced for ordinary & light occupancies. Fire sprinkler spacing to be a maximum of 130 sq. ft. & 256 sq. ft. in light hazard areas.
- Work shall include all materials, labor, plans and plan submittal, rough & final fire sprinkler inspections.
- Fire sprinklers in new scope of work to be new quick response per NFPA 13 2013.
- Fire sprinkler riser to include electronic flow switch, and electronic 10-inch fire bell (installation of bell by others & wiring to bell and flow switch also to be done by others).
- All above ground piping shall be steel sch. 7, 10, 30 & 40 with threaded and or grooved/mechanical fittings.