PROJECT: Inogen - Goleta

PROJECT STATS

    • Industry
    • Industrial
    • Location
    • Goleta, CA

Project Overview

Inogen – Goleta

Scope of Work

  • Provide installation of a new overhead fire sprinkler system throughout proposed warehouse, as shown on provided plans and specifications. 
  • Install into open web joists. 
  • Sprinkler cover to cover new mezzanine per plans and specs and clouded areas labeled. 
  • Building construction is type III-B & approximately 45,000 ft.² in total area floor area. Systems to comply with the County of Santa Barbara Fire Department as well as NFPA-13, 2016 requirements for F-1, B occupancies.  
  • Design: 
  • Warehouse to be ESFR system with 12 heads flowing at 20psi.  
  • Warehouse to be ordinary hazard II .20@1500sqft 

 

  • Precision Fire’s point of connection to be 6” underground @ 6” above finished grade. 
  • Fire sprinkler riser to include electronic flow switch, and electronic 10-inch fire bell (installation of bell by others & wiring to bell and flow switch also to be done by others) 
  • Fire sprinklers in new scope of work to be new quick response per NFPA 13 2019. 
  • All above ground piping shall be steel sch. 7, 10, 30 & 40 with threaded and or grooved/mechanical fittings.  
  • Work shall include all materials, labor, plans and plan submittal, city business license, rough & final fire sprinkler inspections. 
  • Design-Build Engineering will be provided with our services. 
  • Copies of Permits & Approved Fire Sprinkler Plans to be provided to Client upon request. 
All ()
Commercial ()
Residential / Hospitality ()
Industrial ()
Education ()